LS 4
Circuit Breaker Control & Protection
The LS 4 offers a simple solution for complex switchgear applications. The LS 4 has the ability to operate with up to 14 GCP-31 genset controls and 8 LS 4 circuit breaker controllers.
A two line LC display shows the configured names of the analog measuring inputs.
Each controlled breaker is equipped with one LS 4 that measures the three-phase voltage on either side of the breaker (phase angle configurable). Each side of the breaker is designated as either a fixed (utility) or variable (genset) source. This permits the LS 4 to control utility feeder breakers with one fixed source and one variable source, or tie breakers between busses with two variable sources. The LS 4 is used for breaker protection, synchronization, and load control.
View LS 4 H connection application
View LS 4 double H connection application
View LS 4 H multiple incomings application
Product Features:
- True RMS voltage (A and B side)
- True RMS current (A side)
- Synch-check functionality
- Dead bus start functionality
- Synchronous networks functionality
- Remote control of frequency, voltage, and real power
- Zero power transfer control (softload)
- Configurable trip/control set points
- Config. delays for each alarm
- 7 configurable relay outputs
- Two-line LC display
- Synchronization over transformer possible
- CAN bus communication
Protection Functions:
- Overvoltage (ANSI #59)
- Undervoltage (ANSI #27)
- Overfrequency (ANSI #81O)
- Underfrequency (ANSI #81U)
- Phase/vector shift (ANSI #78)
- df/dt ROCOF (rate of change of frequency) (ANSI #81RL)
Certifications / registrations: UL/cUL, CE

Download Technical Documentation
1. To download technical documentation please register here first.
2. Already registered? Login here.
3. After successful login - return to this page and click here to start the download section.