MFR 13

Multi-Function Protection Relay

The MFR 1 Series is a family of industrial grade protective relays that offer multiple protective features in a single package.
Using a digital processor to measure true RMS values enables a high degree of measuring accuracy regardless of harmonics, transients or disturbing pulses.

View MFR 1 series application overview

 

The MFR 13 model is a complete generator protection unit packaged into one compact device. Typical applications are generators and switchgear equipment that require independent protection architecture. Different packages offer additional functionality.

 

Common Features:

  • True RMS generator voltage measurement
  • True RMS generator current measurement
  • kWh metering
  • Configurable trip/control set points
  • Configurable delays for each alarm
  • Two-line Liquid Crystal display
    • Operation and alarm indication
    • Display of measured values
    • English/German display language
  • PC and front panel configurable

 

Common Protection Functions: 

  • Over-/undervoltage (ANSI# 59/27)
  • Over-/underfrequency (ANSI# 81O/U)
  • Voltage assymetry (ANSI# 47)
  • Zero voltage monitoring
  • Overload (ANSI# 32)
  • Reverse power (ANSI# 32R)
  • Reduced power (ANSI# 32F)
  • Unbalanced load (ANSI# 46)
  • Reactive power
  • Loss of excitation (ANSI# 40Q)
  • Independent time-overcurrent (ANSI# 50/51)
  • Inverse time-overcurrent (IEC 255)
  • Inverse time-overcurrent with voltage restraint (ANSI# 51V)

 

MFR 13/GP Features:

  • 3 configurable relays
  • Ground fault (calculated) protection (ANSI# 50GS/51GS)

 

MFR 13/GPX Features: 

  • 8 configurable relays
  • True RMS busbar voltage measurement
  • Synch-check


MFR 13/GPX-I Features: 

Same features as MFR 13/GPX, plus:

  • RS-485 Modbus RTU Slave interface


MFR 13/K08 Features: 

Same features as MFR 13/GPX-I, plus:

  • Ground fault (calculated) protection
  • No GL approval!

 
MFR 13/GPY-I Features: 

Same features as MFR 13/GPX-I, plus:

  • 3 analog outputs -20/0/4 to 20 mA (configurable)
  • Pulse output for kWh


MFR 13/GPY-I-N Features: 

Same features as MFR 13/GPY-I, but:

  • Wide-range power supply (90 to 265 Vac/dc)
  • No UL/cUL listing!

 

Certifications / registrations: UL/cUL, CE, GL

 CU     CE     GL

 

Download Technical Documentation

1. To download technical documentation please register here first.
2. Already registered? Login here.
3. After successful login - return to this page and click here to start the download section.
 

 

Download Certificates:

GL - Germanischer Lloyd

 

Download LeoPC1 Configuration Files:

Refer to the configuration files download page for other P/Ns

 

Download LeoPC1 Configuration Program

 

Please refer to the Woodward Worldwide Directory and contact your local sales office for questions about pricing and delivery or product support.

Return to top of the page

Note: Information contained herein is intended for and appropriate to the purposes of this publication. Woodward reserves the right to update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and applications.

Document Actions
Woodward Home | Search | SiteMap | Contact and Support | Copyright and Terms of Use